Mini Split Size Calculator

Add each room as a zone with its area, sun and ceiling height, pick your climate and insulation, and get the head size for every zone, the multi-zone total, the outdoor unit that covers it, and the power each head draws at your SEER2.

Zones

name · sq ft · sun · ceiling ft

ZoneLoadHead sizeDraw at SEER2 20
Living room10,000 BTU/h12K600 W
Bedroom6,000 BTU/h6K300 W

Heads total

18,000 BTU/h

1.5 tons across 2 zones

Outdoor unit

18K

multi-zone condensers are rated 18K-48K; larger loads need two

Standard sizes

6 / 9 / 12 / 18 / 24 / 30 / 36 / 48

K BTU/h

Standard head sizes and the room they fit

Average conditions, 8 ft ceilings, moderate climate. Watts are full-output draw at the SEER2 shown.

SizeTonsRoom areaWatts @ SEER2 16Watts @ SEER2 22Typical circuit
6K BTU/h0.50up to 250 sq ft37527315 A / 240 V
9K BTU/h0.75250–400 sq ft56340915 A / 240 V
12K BTU/h1.00400–550 sq ft75054515 A / 240 V
18K BTU/h1.50550–800 sq ft1,12581820 A / 240 V
24K BTU/h2.00800–1,000 sq ft1,5001,09120–25 A / 240 V
30K BTU/h2.501,000–1,300 sq ft1,8751,36425–30 A / 240 V
36K BTU/h3.001,300–1,500 sq ft2,2501,63630 A / 240 V
48K BTU/h4.001,500–2,000 sq ft3,0002,18240–50 A / 240 V

Circuit sizes are typical; the nameplate's Minimum Circuit Ampacity and Maximum Overcurrent Protection govern.

Sizing a multi-zone system

  1. Size each room as its own zone with the calculator, rounding up to a standard head.
  2. Add the heads. That is the maximum the outdoor unit should ever be asked for.
  3. Decide whether the zones peak together. Open-plan living and kitchen: yes. Bedrooms versus living room: usually not.
  4. Pick an outdoor unit between 80% and 100% of the sum accordingly, within the manufacturer's allowed connection ratio.
  5. Check the smallest head: many multi-zone condensers cannot modulate low enough for a 6K head in a small bedroom, which then short-cycles. A separate single-zone unit for small rooms is sometimes the better design.

Heating with a mini split

Most mini splits are heat pumps, and the heating load in a cold climate is usually larger than the cooling load for the same room: 45-60 BTU/h per square foot against 20-25. Size the head for the larger of the two, and check the unit's rated capacity at 5°F or −15°F rather than at 47°F -- a "12K" head may deliver 7K at −5°F. Cold-climate models (often branded Hyper-Heat or similar) hold 70-100% of rated output down to −13°F and are worth the premium north of climate zone 5.

Frequently Asked Questions

What size mini split for a 300, 500 or 1,000 sq ft space?

Roughly: up to 250 sq ft a 6K or 9K head; 250-400 sq ft 9K; 400-550 sq ft 12K; 550-800 sq ft 18K; 800-1,000 sq ft 24K; 1,000-1,500 sq ft 30K-36K. Those are average rooms in a moderate climate with 8 ft ceilings; a sunny great room with a vaulted ceiling in Phoenix can need a size up.

Can one mini split cool a whole house?

A single head cools the room it is in and whatever air can circulate to it; closed bedrooms down a hall will not get much. A multi-zone system with a head in each main space is how mini splits cover a whole house, and the calculator adds the zones up so you can size the outdoor unit.

Should I oversize a mini split?

Less than you would think. Inverter mini splits modulate down to about 25-30% of rated capacity, so they tolerate mild oversizing better than fixed-speed units, but a 24K head in a 12K room still short-cycles, dehumidifies poorly and costs more. Size to the load; if you are between sizes and the space is used for heating in a cold climate, go up; if cooling in a humid one, go down.

How much power does a mini split use?

Rated BTU/h divided by SEER2 gives watts at full output: a 12K head at SEER2 20 draws about 600 W, an 18K about 900 W. Because inverters modulate, average draw over a day is usually half that or less. A 12K unit is normally on a 15 A, 240 V circuit; 18K-24K on 20 A; check the nameplate MCA and MOP.

Multi-zone: should the outdoor unit equal the sum of the heads?

Manufacturers allow the heads to add up to 100-130% of the outdoor unit's rating, since not every room peaks at once. If every zone will run flat out together on the hottest day, match the sum; if bedrooms are used at night and living areas by day, an outdoor unit at 80-90% of the sum is normal.

These calculators use National Electrical Code tables and industry sizing charts and are for planning. They are not a substitute for a licensed electrician, an HVAC contractor's Manual J load calculation, or your local code, which governs. Electrical work can kill you and may require a permit; when in doubt, hire it out.