Watts MathAbout

Voltage Drop Calculator

Pick the wire size and material, the system voltage and phase, the load current and the one-way run length. You get the drop in volts and percent against the NEC 3% and 5% recommendations, and the voltage that actually arrives at the load.

Panel to load. The calculator doubles it for the return conductor.

Voltage drop

5.79 V

Percent drop

4.82%

Over 3%: acceptable only if the feeder adds under 2%

Voltage at the load

114.2 V

12 copper ampacity

25 A

NEC 310.16, 75°C

Formula: 2 × 100 ft × 15 A × 1.9300 Ω/kft ÷ 1000 = 5.79 V. Resistance from NEC Chapter 9 Table 8 (DC, 75°C); AC reactance is negligible below 1/0 AWG.

Maximum one-way run for 3% drop, copper, 120 V

Feet of run at which each gauge reaches 3% drop at the current shown (single-phase). Double the distances for 240 V.

AWG10 A15 A20 A30 A40 A50 A
1458 ft39 ft29 ft
1293 ft62 ft46 ft
10148 ft99 ft74 ft49 ft
8235 ft157 ft117 ft78 ft58 ft47 ft
6366 ft244 ft183 ft122 ft91 ft73 ft
4584 ft389 ft292 ft194 ft146 ft116 ft
2927 ft618 ft463 ft309 ft231 ft185 ft
1/01475 ft983 ft737 ft491 ft368 ft295 ft

Dashes: current exceeds the conductor's 75°C ampacity, so the question does not arise.

Percent drop at 20 A, 120 V, by gauge and run

AWG (copper)25 ft50 ft75 ft100 ft150 ft200 ft300 ft
142.6%5.1%7.7%10.2%15.3%20.5%30.7%
121.6%3.2%4.8%6.4%9.6%12.9%19.3%
101.0%2.0%3.0%4.0%6.0%8.1%12.1%
80.6%1.3%1.9%2.5%3.8%5.1%7.6%
60.4%0.8%1.2%1.6%2.5%3.3%4.9%

Amber: over 3%. Red: over 5%. 14 AWG is shown for the arithmetic; it is limited to a 15 A breaker by NEC 240.4(D).

Conductor resistance used (NEC Chapter 9, Table 8)

SizeCopper Ω/kftAluminum Ω/kftCu ampacity 75°CAl ampacity 75°C
143.075.0620 A
121.933.1825 A20 A
101.21235 A30 A
80.7641.2650 A40 A
60.4910.80865 A50 A
40.3080.50885 A65 A
30.2450.403100 A75 A
20.1940.319115 A90 A
10.1540.253130 A100 A
1/00.1220.201150 A120 A
2/00.09670.159175 A135 A
3/00.07660.126200 A155 A
4/00.06080.1230 A180 A
250 kcmil0.05150.0847255 A205 A
300 kcmil0.04290.0707285 A230 A
350 kcmil0.03670.0605310 A250 A
400 kcmil0.03210.0529335 A270 A
500 kcmil0.02580.0424380 A310 A

DC resistance at 75°C, uncoated conductors. For AC circuits above about 1/0 AWG, reactance adds to the impedance and the NEC Table 9 values should be used; below that the difference is within a few percent.

Frequently Asked Questions

What is the voltage drop formula?

For single-phase or DC: Vdrop = 2 × L × I × R ÷ 1000, where L is the one-way length in feet, I the current in amps and R the conductor resistance in ohms per 1,000 ft from NEC Chapter 9 Table 8. The 2 accounts for the return conductor. For three-phase, replace the 2 with √3 (1.732). Percent drop is Vdrop ÷ system voltage × 100.

What is the maximum allowable voltage drop?

The NEC does not mandate a limit for most circuits; the informational note to 210.19(A) recommends no more than 3% on a branch circuit and 5% for the feeder and branch circuit combined. Some jurisdictions and energy codes make the 3% and 5% mandatory. Motors and electronics are the loads that suffer most: a motor at 90% voltage draws more current and runs hot.

How far can I run 12 gauge wire on a 20 amp circuit?

At a full 20 A on 120 V, 12 AWG copper stays under 3% out to about 46 feet one way. At 240 V the same wire and current reach about 93 feet, because the same volts dropped are a smaller share. Most 20 A circuits never carry 20 A continuously, so real runs are often longer; size for the load you actually expect.

Does voltage drop matter for a 12 V or 24 V system?

More than anywhere else. Three percent of 12 V is 0.36 V, which a few feet of thin wire at 10 A will consume. That is why solar, RV, boat and automotive wiring uses much heavier gauge than the current alone would suggest, and why the calculator lets you pick DC and low voltages.

Copper or aluminum?

Aluminum has about 1.6 times the resistance of copper for the same gauge, so it needs to be roughly two sizes larger to match. It is common and code-compliant for service entrances and large feeders where the cost saving is real; it needs the right terminations and anti-oxidant. For branch circuits under 8 AWG, copper is the norm.

These calculators use National Electrical Code tables and industry sizing charts and are for planning. They are not a substitute for a licensed electrician, an HVAC contractor's Manual J load calculation, or your local code, which governs. Electrical work can kill you and may require a permit; when in doubt, hire it out.

More Calculators